Description
This 18 AWG DataBus® Foundation Fieldbus cable provides reliable signaling for process automation. It features stranded tinned copper conductors with Polypropylene (PP) insulation and an overall Beldfoil® shield (100% coverage) for EMI protection. The flexible construction includes a 20 AWG tinned copper drain wire for grounding and a rugged, orange PVC jacket that is sunlight- and oil-resistant for tray, conduit, or outdoor use.
Applications
3076F is designed for exposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Foundation Fieldbus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.
Construction
- 18 AWG stranded (7x26) tinned copper
- 1 twisted pair: blue and orange
- Polypropylene (PP) insulation
- Overall Beldfoil® aluminum-polyester foil shield, (100% coverage)
- 20 AWG stranded (7x28) tinned copper drain wire
- Orange PVC (Polyvinyl Chloride) outer jacket with ripcord
Standards and Compliance
- Environmental Suitability: indoor, outdoor, sunlight resistance, oil resistance, burial
- Flammability / Fire Resistance: UL 1685 (UL Loading), FT4, IEEE 1202, IEC 60332-1-2
- CPR Compliance:CPR Euro class:Eca; CPR UKCA Class: Eca
- NEC / UL Compliance: PLTC, ITC, CM, TC, Article 725, Article 727, Article 800
- CEC / C(UL) Compliance: CMG
- ISO/IEC Compliance: IEC 61158-2
- European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
- UK Regulation Compliance: UKCA Mark
- Other Standard Compliance(s): ISA/SP-50 Type A
Click here for the Belden 3076F Technical Data Sheet .