This 1 AWG, 3-conductor VFD motor supply tray cable (TC-ER) from Belden Basics features segmented bare grounding conductors, providing a robust, standard construction solution for variable frequency drive installations where superior grounding and noise control are critical.
Overall dual bare copper tape shields helically applied with 100% coverage for crack resistance and high frequency noise conduction.
The Exposed Run (TC-ER) rating means this cable meets crush and impact requirements, so it can be installed outside of a cable tray without continuous mechanical protection, unlike standard tray cables that must be enclosed in conduit, raceway, or similar protective systems.
Applications
29528C is designed for use as a variable frequency drive (VFD) cable, AC motor and drive system, Class 1 Division 2 Locations
Construction
- 3 conductors, 1 AWG (19x14) bare copper
- 3 segmented ground wire, 10 AWG (7x18) bare copper (3 totaling 5 AWG)
- XLPE (cross-linked polyethylene) insulated conductors, black and numbered
- Overall dual bare copper tape shield helically applied, 100% coverage
- Black PVC (polyvinyl chloride) outer jacket with ripcord
Standards and Compliance
- Environmental Suitability: Indoor, Outdoor, Sunlight Resistant, Burial
- Sustainability: CA Prop 65
- Flammability / Fire Resistance: UL 1685 UL Loading, IEEE 1202 FT4
- NEC / UL Compliance: Article 336, Type TC-ER, XHHW-2
- ICEA Compliance: S-95-658
- European Directive Compliance: EU CE Mark; EU Directive 2015/863/EU (RoHS 2 amendment); EU Directive 2011/65/EU (RoHS II); EU Directive 2012/19/EU (WEEE)
- APAC Compliance: China RoHS II (GB/T 26572-2011)
- Other Standard Compliance: P-07-KA070003-MSHA