Description
This 16 AWG DataBus® Fieldbus cable provides reliable signaling for process automation and industrial communication systems. It features two stranded tinned copper conductors with Polypropylene (PP) insulation, plus an overall Beldfoil® shield and 65% tinned copper braid shield for EMI protection. The construction includes a 20 AWG tinned copper drain wire for grounding and a rugged orange PVC jacket rated for sunlight, oil, outdoor, and direct burial use.
Applications
1335A is designed for harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.
Construction
- 16 AWG stranded (7x24) tinned copper conductor
- 2 conductors: blue and orange
- Polypropylene (PP) insulation
- Overall Beldfoil® aluminum-polyester foil shield, (100% coverage)
- 20 AWG stranded (7x28) tinned copper drain wire
- Tinned copper braid shield (65% coverage)
- Orange PVC (Polyvinyl Chloride) outer jacket with ripcord
Standards and Compliance
- Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
- Flammability / Fire Resistance: UL 1685 (UL Loading), FT4, IEEE 1202, IEC 60332-1-2
- CPR Compliance:CPR Euro class: Eca; CPR UKCA Class: Eca
- NEC / UL Compliance: PLTC, ITC, CM, TC, Article 725, Article 727, Article 800
- CEC / C(UL) Compliance: CM
- European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
Click here for the Belden 1335A Technical Data Sheet .