Description
This 16 AWG 12 pair extended run instrumentation cable is designed for industrial control and signal transmission in raceways, cable trays, and ducts. It features stranded bare copper conductors with PVC/Nylon insulation, an overall Beldfoil® shield with 100% coverage, a 16 AWG tinned copper drain wire, and a black PVC jacket.
The Exposed Run (ER) rating on this cable means it meets crush and impact testing requirements, and is therefore tough enough to run outside a cable tray without additional protection, unlike standard tray cables which must be installed inside a conduit, raceway or other protection.
Applications
1072A is designed for use in industrial control, raceways, cable trays and ducts, digital control, instruments (4-20ma, 0-10v, ...), low voltage digital control (24v, …), encoders, control circuits, distributed control systems (DCS), programmable logic controllers (PLC), solenoids, valves, actuators and positioners.
Construction
- 16 AWG stranded (7x24) bare copper conductors
- 12 pairs: black, white, and numbered
- Polyvinyl Chloride and Nylon (PVC-NYL) insulation
- Overall Beldfoil® shield (100% coverage)
- 16 AWG stranded (7x24) tinned copper drain wire
- Black Polyvinyl Chloride (PVC) jacket with ripcord
Standards and Compliance
- Environmental Suitability: Indoor/Outdoor, Sunlight Resistance, Burial
- Flammability / Fire Resistance: UL 1685 FT4 Loading, IEEE, 1202, FT4
- NEC / UL Compliance: Article 336, Article 760, NPLF, TC-ER
- European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (ROHS II), EU Directive 2012/19/EU (WEEE)
- APAC Compliance: China RoHS II (GB/T 26572-2011)
Click here for the Belden 1072A Technical Data Sheet.